Non-condensable in the system will result in high head pressure / condensing temperature and occasionally high side pressure fluctuations as well as decreased cooling capacity and efficiency due to higher compression ratios.Click to see full answer. Thereof, what will non Condensables cause?Non-condensables are always caused by improper system evacuation during an installation or repair. These poor procedures leave air, nitrogen, or moisture in the system. If a system has subcooling, superheat, and system pressures/temperatures that simply don’t make sense, suspect that non-condensables are in the system.Similarly, what is non Condensables? Non-condensables are gases that will not condense into a liquid within the operating temperatures of the refrigeration system. Air and nitrogen are the most likely non-condensables you will see. Consequently, how do you remove non Condensables from a refrigeration system? To remove NCGs from refrigerant in smaller systems, recover the entire charge and recharge with fresh refrigerant. It is hard to get to the vapor space in the condenser without tapping a line. To remove NCGs from refrigerant in larger systems, use the nearest access valve to the vapor inlet to the condenser.What happens if air gets in AC system?When air enters a refrigeration system, it collects in the top of the condenser and is trapped. Air will cause a reduction in condenser surface area, which will cause a high condensing pressure. Air can enter the refrigeration system through a leak in the low side of the refrigeration system.